Jun 27, 2017 · for more details please refer to: Aug 10, 2023 · when using a plc recommend to clear the fault by monitoring bit 4 (or digit 5) in parameter b006 [drive status], once the bit is set to 0, than send a clear fault from the logic. A fault f059 [safety open] on a powerflex 525 drive can indicate that both of the safety inputs (safety 1, safety 2) are not enabled. Pin 1 of terminals tb1 connected to ground will also. A fault f059 (safety open) on a powerflex 525 drive can indicate that both of the safety inputs (safety 1, safety 2) are not enabled.
If you are getting this fault while you expect the safety to be on, them you have to figure out why you are losing 24v on s1 and s2. Keep in mind, when you are troubleshooting, if you only lose. Jan 10, 2017 · there is no automatic fault reset for this. You can wire in a fault reset push button or reset from the face of the vfd. Aug 6, 2020 · the drive will stop and show an f059 fault (depending on parameter t105). At this point the fault will need to be reset and another false to true transition of the start signal will. Jul 7, 2021 · resetting the f059 and the f111 fault. After the terminal blocks have been satisfied you can reset the faults: F111 must power cycle if the firmware revision of the powerflex 525.